11.12 Diagnosis of AS-Interface modules for base mounting
SIRIUS ACT 3SU1 pushbuttons and signaling devices
294 System Manual, 08/2018, A5E03457306020A/RS-AK/010
11.12
Diagnosis of AS-Interface modules for base mounting
Status display
The status of a module is indicated by LEDs with continuous or flashing light. This enables
diagnostics at a glance:
For AS-i communication via a red and green LED.
The following chapters provide an overview of the LED status displays of the AS-i modules.
Status display AS-i / FAULT
All modules have green and red LEDs for the "AS-i / FAULT" status display. For the
functions and remedies, see the table below:
Table 11- 3 Diagnostics of the AS-i status via LEDs
AS-i / FAULT
(green / red)
Possible cause
Possible remedial measures
Green Normal operation,
AS-i communication OK
Green
Red
No AS-i communication:
Master is switched off or offline
Ensure AS-i communication:
Switch on the master or switch it to online
mode
Slave is not configured in the master Reconfigure the master
Incorrect slave type connected Connect the correct module
Slave has the wrong address Check/correct the slave address
Flashing green
Red
Module has slave address "0"
(delivery condition)
Assign an address other than "0"
Flashing
alternately
green/red
1
Overload of the outputs Disconnect actuator cables
Check actuators and cables
OFF
No AS-i voltage
Switch on AS-i voltage
AS-i voltage has been connected with reverse
polarity
Connect it correctly
AS-i voltage too low Measure the AS-i voltage (approx. 24 V DC or
30 V DC)
1
Only 4DI/4DO and 4DI/3DOAB modules