IO-Link 3SU14
12.2 Electronic modules for ID key-operated switches
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 08/2018, A5E03457306020A/RS-AK/010
335
12.2.7
Diagnostics
12.2.7.1
IO-Link diagnostics
IO-Link diagnostics
On the electronic modules for ID key-operated switches for IO-Link, it is possible to carry out
diagnostics via IO-Link. Short-circuit is signaled via the diagnostics mechanism of IO-Link.
With all further diagnostics messages, the corresponding bit is set in data set (index) 92 -
diagnostics.
The table below provides information on possible causes and remedial measures:
Table 12- 7 Possible causes and remedial measures
Diagnostics and messages
Possible cause
Possible remedial measures
Short-circuit
The electrical cable connection on at
least one of the digital outputs has been
short-circuited.
The connected actuator is defective.
The current consumption of the
connected actuator is too high.
Check the electrical cable
connection of the digital outputs.
Check the current consumption of
the connected actuator.
Use a new actuator.
Self-test error / internal error
Fault in internal test.
The data saved in the device are
invalid.
Reset the electronic module to
the delivery state and reconfigure
the electronic module.
Return the device to the
manufacturer.
Individually codable ID key cannot be
saved:
Key list is full
50 individually codable keys have already
been saved, and the available memory
range is full.
Check the data in data sets 81
and 82 (memory of the
individually codable ID keys
(1-30) - data set (index) 81, and
memory of the individually
codable ID keys (31-50) - data set
(index) 82)
Delete the no longer used
individually codable ID keys from
the memory.
Individually codable ID key cannot be
saved:
invalid key
No valid individually codable ID key
inserted.
The inserted individually codable ID key
is defective.
Use an individually codable
ID key if, for example, a colored
ID key has been inserted.
Use another individually codable
ID key since the inserted ID key
could be defective.
Check that the ID key has been
inserted as far as it will go.