IO-Link 3SU14
12.1 Configuring the IO-Link
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 08/2018, A5E03457306020A/RS-AK/010
307
12.1.3.3
Configuration
Configuring the IO-Link device with the S7-PCT port configuration tool
1. Start the
S7-PCT
port configuration tool.
2. Create a new project or open an existing project as described in the online help.
3. Select a bus category (PROFIBUS DP/PROFINET IO).
4. Select an IO-Link master.
5. Select the IO-Link device in the component catalog of the
S7-PCT
port configuration tool.
6. Drag the IO-Link device out of the component catalog to the required port of the IO-Link
master.
7. Load the configuration into the IO-Link master before parameterizing the IO-Link device.
8. Start by parameterizing the IO-Link device.
Additional information is available in the
S7-PCT
online help.
Note
To be able to access the IO
-Link master or an IO-Link device online, communication
between the ET
200 and the higher-level controller must be active (BF LED on ET 200
interface module is off).
12.1.4
Acyclic data exchange with the IO_LINK_MASTER function block
For acyclic data exchange, the IO_LINK_MASTER function block is available as a download
for controllers of the S7 families.
With the help of this block, you can back up or restore the device parameters and settings of
an IO-Link communication module (e.g. ET 200SP CM 4xIO-Link) via the S7 program.
Requirements
Install the IO_LINK_MASTERfunction block.
You can download the IO_LINK_MASTER function block and the description from the
Internet (https://support.industry.siemens.com/cs/ww/en/view/82981502
).
Procedure when using the IO_LINK_MASTER function block
1. Copy the IO_LINK_MASTER function block (including data block DB10) to a
STEP 7
project.
2. Use the IO_LINK_MASTER function block as described in the documentation.