IO-Link 3SU14
12.2 Electronic modules for ID key-operated switches
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 08/2018, A5E03457306020A/RS-AK/010
315
Settings on the electronic module for ID key-operated switches
The electronic modules for ID key-operated switches have 5 digital outputs. Setting of
outputs 0 to 3 depends on the current key position and the module settings. If a valid ID key
has been recognized, output 4 is active; otherwise output 4 is inactive.
Table 12- 1 Individual method
Key position
Output
0
1
2
3
0
Inactive
Inactive
Inactive
Inactive
1
Active
Inactive
Inactive
Inactive
2
Inactive Active Inactive Inactive
3
Inactive
Inactive
Active
Inactive
4
Inactive
Inactive
Inactive
Active
Table 12- 2 Addition method (incremental method)
Key position
Output
0
1
2
3
0
Inactive
Inactive
Inactive
Inactive
1
Active
Inactive
Inactive
Inactive
2
Active
Active
Inactive
Inactive
3
Active
Active
Active
Inactive
4
Active
Active
Active
Active
Note
The addition
method (incremental method) can only be set on the electronic modules for ID
key
-operated switches for IO-Link.
Short-circuit protection
If a short-circuit occurs at one or more outputs, the occurrence of a fault event is sent and
the fault flag is set. All outputs are deactivated for one second. Then the relevant outputs are
re-activated to monitor whether the short-circuit is still active. This temporary state exists for
approximately 0.1 seconds. If no short-circuit is determined during this period, the fault event
is revoked, and the fault flag is deleted. However, if a short-circuit is detected during this
time, all outputs are deactivated again, and the short-circuit device fault remains.