IO-Link 3SU14
12.3 Electronic modules for IO-Link
SIRIUS ACT 3SU1 pushbuttons and signaling devices
342 System Manual, 08/2018, A5E03457306020A/RS-AK/010
Article numbers
Front plate mounting
(https://mall.industry.siemens.com/mall/en/WW/Catalog/Products/10221531
)
Base mounting (https://mall.industry.siemens.com/mall/en/WW/Catalog/Products/10251420)
Mounting type
Digital inputs
Digital outputs
Article number
Front plate mounting 6
1)
2
1)
3SU1400-1HL10-6AA0
Base mounting
6
1)
2
1)
3SU1400-2HL10-6AA0
Base mounting
6
2)
2
2)
3SU1400-2HK10-6AA0
Base mounting
4
2)
4
2)
3SU1400-2HM10-6AA0
Base mounting 2
2)
6
2)
3SU1400-2HN10-6AA0
1)
Default setting. The 8 digital inputs and outputs can be parameterized individually as
required.
2)
It is not possible to change the number of inputs and outputs.
Short-circuit protection
If a short-circuit occurs at one or more outputs, the occurrence of a fault event is sent and
the fault flag is set. All outputs are deactivated for one second. Then the relevant outputs are
re-activated to monitor whether the short-circuit is still active. This temporary state exists for
approximately 0.1 seconds. If no short-circuit is determined during this period, the fault event
is revoked, and the fault flag is deleted. However, if a short-circuit is detected during this
time, all outputs are deactivated again, and the short-circuit device fault remains.