EasyManua.ls Logo

Smartrise C4

Default Icon
400 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C4 User Manual
Page 306 ©2021 Smartrise Engineering, Inc. All Rights Reserved October 25, 2021
4. From the MR 2 SMOKE menu, scroll and select Shunt Trip.
Figure 606: MR 2 SMOKE Menu Shunt Trip
5. From the SHUNT ON RECALL menu, scroll and select On. See Figure 602.
6. Scroll right and press Save.
33.3.10 Advanced Configs
Advanced configuration is a simple way to configure specific fire parameters within the system.
For a description of each parameter, see the C4 Parameter List.
The following is a list of the specific parameters that can be configured.
RESET TO EXIT PHASE 1
DIS RSTCTR ON PHASE 2
PHASE 2 SWING REOPEN DISABLED
EXIT PHASE 2 ONLY AT RECALL FLOOR
IGNORE LOCKS JUMPED ON PHASE 2
FIRE STOP SWITCH KILLS DOOR OPERATOR
DOL TO EXIT PHASE 2
EXIT PHASE 1 AT MAIN RECALL ONLY
OK TO STOP OUTSIDE DOOR ZONE
ALLOW RESET WITH ACTIVE SMOKE
HAT FLASH IGNORE ORDER
MOMEMNTARY DOOR CLOSE BUTTON
FLASH LOBBY FIRE LAMP
REMOTE AND MAIN TO OVERRIDE SMOKE
ENABLE PHE ON PH2
DOOR OPEN ON HOLD
The following procedure describes how to configure specific parameters listed in Advanced
Configuration.
1. Navigate to MAIN MENU | SETUP | FIRE. See Figure 57.

Table of Contents

Other manuals for Smartrise C4

Related product manuals