EasyManua.ls Logo

Solar-Log 2000 - 70% Fixed Reduction with the Calculation of Self-Consumption

Solar-Log 2000
224 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
150
Feed-In Management
Procedure
Select 70% fixed reduction.
Select the inverter(s) to control in the Interface assignments section.
SAVE the settings.
Note!
Changes to the Maximum AC Power of the inverter in Configuration | Devices | Con-
figuration menu are disabled.
Enter your password via the Log-on as Installer / PM to enable changes.
Note!
The 70% reduction is always applied to the entire plant.
All of the inverters are controlled on the same level by the Solar-Log™, independent of
their alignments (east-west orientation). This can lead to a lower feed-in amount than
the maximum allowed.
Example 1
DC power 12kWp
AC power 12kW
70% of the DC power corresponds to 8.4kW.
As the AC and DC power are identical, the down-control is correct.
Example 2
DC power 12 kWp
AC power 10kW
70% of the DC power corresponds to 8.4kW.
For this reason the inverter controlled by the Solar-Log™ is reduced to 84% (8.4kW) and not only to 70%
(7kW).
24.2.5 70% Fixed reduction with the calculation of self-consumption
This function is an enhancement to the 70% fixed reduction described in the previous chapter.
The Solar-Log™ needs to be linked to a consumption meter to implement this function. Please note the
instructions in chapter “12.5 External power meter“. The configuration of this corresponds to that already
described for the 70% fixed reduction.
Procedure
Select 70% Fixed reduction with the calculation of self-consumption
Select the inverter(s) to control in the Interface assignments section.
SAVE the settings.
Note!
The Solar-Log™ needs to be linked to a consumption meter to implement this function.
Please note the instructions in chapter„12.5 External power meters“.

Table of Contents

Other manuals for Solar-Log 2000

Related product manuals