Why does OVERLOAD trip occur after Bypass is closed in Solcon Controller?
- TTerri HowardAug 26, 2025
An OVERLOAD trip after Bypass closure in the Solcon Controller can happen due to several reasons: * Verify that current Gain dip switches are set according to the testing motor rated current versus rated current of the starter. Overload trip can occur if gain (set by Gain dip switches settings) is too high. * Verify that the HRVS-DN FLC setting parameter is set according to the rated current of the HRVS-DN. * Set Motor FLA identically to HRVS-DN FLC. * Reset, start again and read currents on screen. * Check if current readings after start are is more than starter’s rated current.