3.
Click the Orphan Mode tab, and select an NTP Stratum other than 15. This will be the
Stratum level SecureSync will transition to in the event its input references become
invalid.
4.
Click Submit. SecureSync will automatically stop and re-start the NTP Service.
Note: Per NTP protocol definition, for an NTP Orphan Mode Timing Network to
operate properly, ALL servers and clients must be set to the same Stratum level
(e.g., "5").
2.15.14 Host Disciplining
Host Disciplining allows an NTP input reference to discipline SecureSync's oscillator. This may
be utilized e.g., with SecureSync units that do not have a GPS receiver because they are oper
ated as Stratum2 servers.
In general, it is advisable to enable Host Disciplining only if needed, and to use it only in
robust networks/NTP environments.
Note that Host Disciplining is NOT supported by SecureSync units equipped with a Rubidium
oscillator.
ON : When Host Disciplining is ON, the NTP reference is used to discipline
SecureSync's oscillator, thus providing more stable oscillator performance.
About system software updates:
When updating to System Software Version 5.4.5, Host Disciplining will fall to its
default setting. When updating to future System Software versions, the last setting will be
carried over to the new software.
In any case, after a system software update it is advisable to verify that Host Disciplining
is still enabled.
126
CHAPTER 2 • SecureSync User Reference Guide Rev. 23
2.15 Configuring NTP

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Spectracom SecureSync 1200 and is the answer not in the manual?

Spectracom SecureSync 1200 Specifications

General IconGeneral
BrandSpectracom
ModelSecureSync 1200
CategoryControl Unit
LanguageEnglish