EasyManuals Logo

Spectracom SecureSync 1200 User Manual

Spectracom SecureSync 1200
581 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #305 background imageLoading...
Page #305 background image
No longer in Holdover: Input references were lost at one point (or declared not valid),
but have since been restored OR the Input references were not restored before the Hol
dover period expired (Time Sync alarm is asserted).
In Sync: SecureSync is synchronized to its Time and 1PPS inputs.
Not In Sync: SecureSync is not synchronized to its Time and 1PPS inputs and is not cur
rently in Holdover. NTP will indicate to the network that it is Stratum 15 and so the time
server likely be ignored as a time reference.
Sending trap for event 1 (SNMPSAD): An SNMP trap was sent by the SNMP agent to
the SNMP Manager. The event number in this entry indicates which SNMP trap was sent.
The Unit has Rebooted: SecureSync was either rebooted or power cycled.
Alarms Log
Displays log entries for the Timing System, for example:
The Unit has Rebooted: SecureSync was either rebooted or power cycled.
In Holdover: Input references were available, but all input references have since been
lost. If the references are not restored before the Holdover period expires, time sync will
be lost.
No longer in Holdover: Input references were lost at one point (or declared not valid),
but have since been restored OR the Input references were not restored before the Hol
dover period expired (Time Sync alarm is asserted).
In Sync: SecureSync is synchronized to its selected Time and 1PPS reference inputs.
Not In Sync: SecureSync is not synchronized to its Time and 1PPS inputs and is not cur
rently in Holdover. NTP will indicate to the network that it is Stratum 15 and so the time
server likely be ignored as a time reference.
Frequency Error: The oscillator’s frequency was measured and the frequency error was
too large. Or, the frequency couldn’t be measured because a valid input reference was
not available.
Reference change: SecureSync has selected a different Time and 1PPS input reference
for synchronization. Either the previously selected input reference was declared not valid
(or was lost), so a lower priority reference (as defined by the Reference Priority Setup
table) is now selected for synchronization OR a valid reference with higher priority than
the previous reference is now selected for synchronization.
E X A M P L E :
GNSS is the highest priority reference with IRIG input being a lower priority. SecureSync is synced to
GNSS and so GNSS is the selected reference. The GNSS antenna is disconnected and IRIG
becomes the selected reference. The Reference change entry is added to this log.
Timing Log
4.5 Quality Management
CHAPTER 4 • SecureSync User Reference Guide Rev. 23