Table 43: Digital input settings
Index Parameter Default ID Description
P3.5.1.23 Preset Frequency Selection 2 DigIN Slot0.1 * 421
P3.5.1.24 Motor Potentiometer UP DigIN Slot0.1 418
OPEN = Not active
CLOSED = Active
P3.5.1.25 Motor Potentiometer DOWN DigIN Slot0.1 417
OPEN = Not active
CLOSED = Active
P3.5.1.26 Quick Stop Activation Varies 1213 OPEN = Activated
P3.5.1.27 Timer 1 DigIN Slot0.1 447
P3.5.1.28 Timer 2 DigIN Slot0.1 448
P3.5.1.29 Timer 3 DigIN Slot0.1 449
P3.5.1.30 PID Setpoint Boost DigIN Slot0.1 1046
OPEN = No boost
CLOSED = Boost
P3.5.1.31 PID Setpoint Selection DigIN Slot0.1 * 1047
OPEN = Setpoint 1
CLOSED = Setpoint 2
P3.5.1.32 External PID Start Signal DigIN Slot0.2 1049
OPEN = PID2 in stop mode
CLOSED = PID2 regulating
P3.5.1.33
External PID Setpoint Selec-
tion
DigIN Slot0.1 1048
OPEN = Setpoint 1
CLOSED = Setpoint 2
P3.5.1.34 Reset Maintenance Counter 1 DigIN Slot0.1 490 CLOSED = Reset
P3.5.1.36 Flushing Reference Activation DigIN Slot0.1 * 530
P3.5.1.38 Fire Mode Activation OPEN DigIN Slot0.2 1596
OPEN = Fire mode active
CLOSED = No action
P3.5.1.39 Fire Mode Activation CLOSE DigIN Slot0.1 1619
OPEN = No action
CLOSED = Fire Mode active
P3.5.1.40 Fire Mode Reverse DigIN Slot0.1 1618
OPEN = Forward
CLOSED = Reverse
P3.5.1.41 Auto-cleaning Activation DigIN Slot0.1 1715
P3.5.1.42 Pump 1 Interlock DigIN Slot0.1 * 426
OPEN = Not active
CLOSED = Active
P3.5.1.43 Pump 2 Interlock DigIN Slot0.1 * 427
OPEN = Not active
CLOSED = Active
P3.5.1.44 Pump 3 Interlock DigIN Slot0.1 * 428
OPEN = Not active
CLOSED = Active
P3.5.1.45 Pump 4 Interlock DigIN Slot0.1 429
OPEN = Not active
CLOSED = Active