P3.2.2 LOCAL/REMOTE (ID 211)
Use this parameter to switch between the local and remote control places.
Local control place is always keypad control. The remote control place can be I/O or
Fieldbus, depending on the 'Remote Control Place' parameter value.
P3.2.3 KEYPAD STOP BUTTON (ID 114)
Use this parameter to enable the keypad stop button.
When this function is enabled, a press of keypad stop button always stops the drive
(regardless of the control place). When this function is disabled, a press of keypad stop
button stops the drive in local control only.
Selection
number
Selection name Description
0 Yes The keypad stop button is always enabled.
1 No Limited function of the keypad stop button.
P3.2.4 START FUNCTION (ID 505)
Use this parameter to select the type of the start function.
Selection
number
Selection name Description
0 Ramping
The drive accelerates from 0 frequency to frequency refer-
ence.
1 Flying start
The drive detects the actual speed of the motor and acceler-
ates from that speed to frequency reference.
P3.2.5 STOP FUNCTION (ID 506)
Use this parameter to select the type of the stop function.
Selection
number
Selection name Description
0 Coasting
The motor stops on its inertia. When the stop command is
given, the control by the drive stops and the current from the
drive goes to 0.
1 Ramp
After the stop command, the speed of the motor is decreased
to zero speed according to the deceleration parameters.
NOTE!
Ramp stop cannot be guarenteed in all situations. If ramp stop is selected and the
net voltage changes over 20%, the voltage estimation fails. In such case, ramp stop
is not possible.
VACON · 232 PARAMETER DESCRIPTIONS
10
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V