PT
Start / Stop
Fig. 8: Multi-pump (single drive) configuration
Autochange function (change of start order) makes the wear of the motors in the system
more equal. Autochange function monitors the running hours and sets the start order of
each motor. The motor that has the lowest running hours starts first and the motor that has
the highest running hours starts last. You can configure the autochange to start based on the
autochange interval time set by the internal real time clock (an RTC battery needed) of the
drive.
You can configure the autochange for all the motors in the system or only the auxiliary
motors.
QUICK STARTUP GUIDE VACON · 31
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
1

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V