EasyManuals Logo

Vacon 100 flow Applications Manual

Vacon 100 flow
386 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
Table 12: M1 Quick setup
Index Parameter Min Max Unit Default ID Description
1.10
Motor Nom-
inal Fre-
quency
8.0 320.0 Hz
50.0 /
60.0
111
Find this value f
n
on
the nameplate of the
motor.
1.11
Motor Nom-
inal Speed
24 19200 Rpm Varies 112
Find this value n
n
on
the nameplate of the
motor.
1.12
Motor Nom-
inal Current
I
H
* 0.1 I
S
A Varies 113
Find this value I
n
on
the nameplate of the
motor.
1.13
Motor Cos
Phi (Power
Factor)
0.30 1.00 Varies 120
Find this value on the
nameplate of the
motor.
1.14
Energy Opti-
misation
0 1 0 666
The drive finds the
minimum motor cur-
rent to use less
energy and to lower
the motor noise. Use
this function with, for
example, fan and
pump processes.
0 = Disabled
1 = Enabled
1.15
Identifica-
tion
0 2 0 631
The identification run
calculates or meas-
ures the motor
parameters that are
necessary for a good
control of the motor
and speed.
0 = No action
1 = At standstill
2 = With rotation
Before you do the
identification run,
you must set the
motor nameplate
parameters.
1.16
Start Func-
tion
0 1 0 505
0 = Ramping
1 = Flying Start
1.17
Stop Func-
tion
0 1 0 506
0 = Coasting
1 = Ramping
QUICK STARTUP GUIDE VACON · 69
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
1

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V