• The disconnection device must be rated 16 A or 20 A at 250 VAC, and must conform to
any additional local regulations.
• To prevent accidental switching on during installation and maintenance, the
disconnection device must be visible from the enclosure, or lockable with a key.
• The installed enclosure must not block access to the disconnection device. The
disconnection device must remain easy to operate.
The AC (mains) cable is not included in the delivery. Use an AC (mains) cable with a
minimum cross-section of 3 × 1.5 mm
2
(15 AWG).
Chapter 17 – Electrical Installation
227