69
EC Card Register (Simple Code) Related to the VS-2PT-EC
EC3
EC1
EC2
EC1D0
EC1D1
EC1D2
EC1D3
EC1D6
EC1D7
EC1D17
EC2D0
EC2D1
EC2D2
EC2D3
EC2D6
EC2D7
EC2D17
EC3D0
EC3D1
EC3D2
EC3D3
EC3D6
EC3D7
EC3D17
To assign the unit of temperature measurement. 0: ; 1: ; other values: .
Converted temperature value of PT1, with unit as 0.1 or 0.1 .
EC1D18
EC1D19
Identication code: K108 (If code = K240, means connecting error between Main Unit and card)
The version number of this card. (the content value XX indicates Ver. X.X)
EC2D18 EC3D18
EC2D19 EC3D19
Converted temperature value of PT2, with unit as 0.1 or 0.1 .
To set the average times of PT1.
To set the average times of PT2.
Status and error ag.
Usable set value is 1~32767; other values = 1.
b0
b1b2
b3
b4
b15b5
Component Description
To select the frequency of power noise to be ltered out. 0: 60Hz, 1: 50Hz; other values: 60H.
Reduce the inuence of noise from power lines. Always set the value as 1 for 50Hz AC system.
Status and Error Flag:
PT1 is disconnected or converted value exceeds the range
The hardware error ag of this card
PT2 is disconnected or converted value exceeds the range