68
EC Card Register (Simple Code) Related to the VS-4TC-EC
EC3
EC1 EC2
Component Description
EC1D0
EC1D1
EC1D2
EC1D3
EC1D4
EC1D5
EC1D6
EC1D7
EC1D8
EC1D9
EC1D17
EC2D0
EC2D1
EC2D2
EC2D3
EC2D4
EC2D5
EC2D6
EC2D7
EC2D8
EC2D9
EC2D17
EC3D0
EC3D1
EC3D2
EC3D3
EC3D4
EC3D5
EC3D6
EC3D7
EC3D8
EC3D9
EC3D17
EC1D18
EC1D19
EC2D18 EC3D18
EC2D19 EC3D19
b15 b0
TC2 TC1
Example: If a VS-4TC-EC is installed at the EC1, and its EC1D0 is set to be H8100, then
TC1 & TC2: K Type of thermocouple input, TC3: J Type thermocouple input, TC4: disabled
TC4 TC3
0
1
2
3
4
5
6
J
K R S T E B
7
N
Status and Error Flag:
b0
b1b2
b3
b4
b15~b5
TC1 is disconnected or converted value exceeds the range
TC4 disconnected or converted
value exceeds the range
The hardware error ag of this card
To assign the thermocouple types for TC1~TC4.
To assign the unit of temperature measurement. 0:℃; 1:℉; other values:℃.
Converted temperature value of TC1, with unit as 0.1 ℃ or 0.1 ℉.
Converted temperature value of TC2, with unit as 0.1 ℃ or 0.1 ℉.
To set the average times of TC1
To set the average times of TC2
Converted temperature value of TC3, with unit as 0.1 ℃ or 0.1 ℉.
Converted temperature value of TC4, with unit as 0.1 ℃ or 0.1 ℉.
To set the average times of TC3
To set the average times of TC4
The version number of this card. (the content value XX indicates Ver. X.X)
Status and error ag
Identication code: K106 (If code = K240, means connecting error between Main Unit and card)
Usable set value is 1~32767; other values =5.
To appoint the types of thermocouples:
Value of Nibble
Thermocouple Type
If Value of Nibble is not 0~7,
the channel is disabled.
TC2 is disconnected or converted value exceeds the range
TC3 is disconnected or converted value exceeds the range
Nibble #4
Nibble #3
Nibble #2 Nibble #1
EC Card Register (Simple Code) Related to the VS-1PT-EC
EC3
EC1 EC2
Component Description
EC1D0
EC1D1
EC1D2
EC1D6
EC1D17
EC2D0
EC2D1
EC2D2
EC2D6
EC2D17
EC3D0
EC3D1
EC3D2
EC3D6
EC3D17
To assign the unit of temperature measurement. 0: ℃ ; 1:℉ ; other values: ℃ .
Converted temperature value of PT1, with unit as 0.1 ℃ or 0.1 ℉ .
EC1D18
EC1D19
Identication code: K107 (If code = K240, means connecting error between Main Unit and card)
The version number of this card. (the content value XX indicates Ver. X.X)
EC2D18 EC3D18
EC2D19 EC3D19
To set the average times of PT1. Usable set value is 1~32767; other values = 1.
Status and error ag
Status and Error Flag:
TC1 is disconnected or converted value exceeds the range
The hardware error ag of this card
To select the frequency of power noise to be ltered out. 0: 60Hz, 1: 50Hz; other values: 60H.
Reduce the inuence of noise from power lines. Always set the value as 1 for 50Hz AC system.
b0
b1b2
b3
b4
b15~b5