Original Operating Instructions
APS Series Outdoor Hybrid Inverter
Installation
APS-Series 120 Operating Instructions v320 EN
Page 120 of 213
4.9.2 MV Skid not monitored by the APS
NOTICE
Failure during grid connections due to missing cable bridge and
resistor!
If the APS used without a MV skid or monitored external, the customer
must connect delivered cable bridge and a resistor.
The cable bridge and resistor located in Section +C3 for
1-2 APUs or Section +C6 for 3-4 APUs.
Use only the delivered cable bridge and resistor.
Procedure:
1. Connect the delivered cable bride and resistor to provided terminals
(Figure 101).
Figure 101: Connection of MV skid interfaces when not monitored by the APS
Pos.
Description
1
MV switchgear simulation ON
2
Resistor simulation PT100