7.2.1 APS Warning Codes 1, 2
Corrective action:
1. See Section 7.1.1.
7.2.2 APS Warning Code 5
Corrective action:
1. It is recommended to replace all AC surge arrester modules (-FA2) (Figure 21)
if the indication shows a red flag.
Open doors in Section +C1.
AC surge arrester is bottom-left on the mounting plate.
Use surge arrester modules from the spare parts list (Table 30).
2. It is recommended to replace all AC surge arrester modules (-FA111)
(Figure 18), if the indication shows a red flag.
Open doors in Section +C3.
AC surge arrester is on the right mounting plate.
Use surge arresters modules form the spare parts list (Table 30).
3. It is recommended to replace all AC surge arrester modules (-FA211)
(Figure 18), if the indication shows a red flag.
Open doors in Section +C6.
AC surge arrester is on the right mounting plate.
Use surge arresters form the spare parts list (Table 30).
7.2.3 APS Warning Code 6
Corrective action:
1. It is recommended to replace all DC surge arrester modules (-FA110.1)
(Figure 20), if the indication shows a red flag.
Open doors in Section +C2.
DC surge arrester is between the plus copper rails.
Use surge arresters modules form the spare parts list (Table 31 or Table
32).
2. It is recommended to replace all DC surge arrester modules (-FA210.1)
(Figure 20), if the indication shows a red flag.
Open doors in Section +C5.
DC surge arrester is between the plus copper rails.
Use surge arresters modules form the spare parts list (Table 31 or
Table 32).
7.2.4 APS Warning Codes 10, 11, 13, 14
Corrective action:
1. Check if there is a short-circuit to ground in the PV field or battery field.