7.1.1 APS Error Codes 3, 4
Corrective action:
1. Check the fluid level (Section 4.4.4).
In case of low fluid level, refill the cooling system up to the fluid level.
2. Open doors in Sections +C3, +C6 (Figure 13).
3. Check all hose couplings and hose connections for leakage.
In case of leakage, please contact customer service (Section 11).
7.1.2 APS Error Code 5
Corrective action:
1. Check if the Enable switch is in position OFF (Figure 13).
If the Enable switch is in position OFF, switch the Enable switch in
position ON.
2. Check if all cabinet doors are closed (Figure 13, Figure 14).
If the cabinet doors are open, close all cabinet doors.
7.1.3 APS Error Code 7
NOTICE: For monitoring the MV switchgear the customer must connect the feedback
contacts (Section 4.9).
Corrective action:
1. Check the MV switchgear.
7.1.4 APS Error Code 8
Corrective action:
1. Start the option heating manually via VNC access (Function and Interface
Description).
2. Check if the heating is ON.
7.1.5 APS Error Code 9
NOTICE: For monitoring the MV switchgear the customer must connect the feedback
contacts (Section 4.9).
Corrective action:
1. Check the MV transformer for short-circuit and internal faults.
2. Check the fluid level of the MV transformer.
If the fluid level is too low, please contact customer service
(Section 11).
7.1.6 APS Error Code 19
Corrective action:
1. Check the +25 V
DC
supply voltage.
Measure the voltage on power supply (-TB1) (Section +C1).