EasyManua.ls Logo

YASKAWA MP920 - D.2.2 Panel-To-Panel Cables; Wiring Separation; Shield Treatment; Exposed Conductor Length

YASKAWA MP920
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix D Wiring Communications
D.2.2 Panel-to-Panel Cables
D-16
D.2.2 Panel-to-Panel Cables
The following table shows the panel-to-panel cables used for communications.
Always use the specified cables. Otherwise, the communications system will fail to provide
its full performance.
When bending a communications cable, be sure that the bending radius is at least 10 times
the finished outer diameter of the cable.
D.2.3 Wiring Separation
• House the shielded communications cables in a low-voltage circuit duct that is different
from general operation circuit ducts. If this is not possible, keep the low-voltage circuits
at least 100 mm away from the general control circuits.
• Likewise, keep the shielded communications cables at least 300 to 1,200 mm from the
main circuits.
D.2.4 Shield Treatment
• Ground the shield at one point only for panel-to-panel cables.
• Using a ground wire of 8 mm
2
or greater, ground the shielded ground trunk cable to an
independent ground pole with a ground resistance of 100 or less.
D.2.5 Exposed Conductor Length
• The exposed conductor length of each panel-to-panel twisted-pair cable should be as
short as possible (100 mm or less).
• The characteristic impedance of the exposed conductor section is greater than the pre-
scribed value (75).
• Increasing the exposed conductor length increases transmission waveform distortion,
resulting in a transmission error.
Table D.3 Cable Bending Radius
Communications
System
Cable Type Finished
Outer
Diameter
dl (mm)
Permissible
Bending
Radius
10 dl (mm)
Applicable Duct
215IF,
217IF RS-485
Twisted-pair cable:
YS-IPEV-S (Cu), 1P × 1.25 mm,
manufactured by Fujikura Corpo-
ration
8.6 86 min.
Low-voltage
duct
CP-215
Repeater
Coaxial cable:
5C-2V (Cu, Fe)-ZV, manufac-
tured by Fujikura Corporation
12.0 120 min.
Low-voltage
duct
100 mm max.
Twisted-pair cable

Table of Contents

Related product manuals