B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual 381
Parameter List
B
n E3: V/f Pattern for Motor 2
These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).
E2-05
(312H)
Motor Line-to-Line Resistance
Sets the phase-to-phase motor resistance. Automatically set during Auto-Tuning.
Default:
<24>
Min: 0.000 Ω
Max: 65.000 Ω
166
E2-06
(313H)
Motor Leakage Inductance
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage.
Automatically set during Auto-Tuning.
Default:
<24>
Min: 0.0%
Max: 40.0%
166
E2-07
(314H)
Motor Iron-Core Saturation
Coefficient 1
Sets the motor iron saturation coefficient at 50% of magnetic flux. Automatically set during
Auto-Tuning.
Default: 0.50
Min: 0.00
Max: 0.50
166
E2-08
(315H)
Motor Iron-Core Saturation
Coefficient 2
Sets the motor iron saturation coefficient at 75% of magnetic flux. Automatically set during
Auto-Tuning.
Default: 0.75
Min: E2-07
Max: 0.75
166
E2-09
(316H)
Motor Mechanical Loss
Sets the motor mechanical loss as a percentage of motor rated power (kW).
Default: 0.0%
Min: 0.0%
Max: 10.0%
167
E2-10
(317H)
Motor Iron Loss for Torque
Compensation
Sets the motor iron loss.
Default:
<24>
Min: 0 W
Max: 65535 W
167
E2-11
(318H)
Motor Rated Power
Sets the motor rated power in kilowatts (1 HP = 0.746 kW). Automatically set during
Auto-Tuning.
Default:
<24>
Min: 0.00 kW
Max: 650.00 kW
167
<18> This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01. The value will
have two decimal places (0.01A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer to Table A.2 and Table A.3)
and one decimal place (0.1A) if the set Maximum Applicable Motor Capacity is higher than 11 kW.
<24> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
No.(Addr.) Name Description Setting Page
E3-01
(319H)
Motor 2 Control Mode Selection
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
Default: 0
Min: 0
Max: 3
168
No.(Addr.) Name Description Setting Page
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV

Table of Contents

Related product manuals