B.3 Parameter Table
382 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
n E4: Motor 2 Parameters
These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).
E3-04
(31AH)
Motor 2 Maximum Output
Frequency
To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the
setting for E3-08 will be disregarded. Ensure that the four frequencies are set according to these
rules or an oPE10 fault will occur:
E3-09 E3-07 < E3-06 ≤ Ε3−11 ≤ E3-04
Note: E3-07 and E3-08 are only available in the following control modes: V/f, V/f w/PG and
OLV.
Default:
<25>
Min: 40.0 Hz
Max: 400.0 Hz
168
E3-05
(31BH)
Motor 2 Maximum Voltage
Default:
<15> <25>
Min: 0.0 V
Max: 255.0 V
<15>
168
E3-06
(31CH)
Motor 2 Base Frequency
Default:
<25>
Min: 0.0 Hz
Max: E3-04
168
E3-07
(31DH)
Motor 2 Mid Output Frequency
Default:
<25>
Min: 0.0 Hz
Max: E3-04
168
E3-08
(31EH)
Motor 2 Mid Output Frequency
Voltage
Default:
<15> <25>
Min: 0.0 V
Max: 255.0 V
<15>
168
E3-09
(31FH)
Motor 2 Minimum Output
Frequency
Default:
<25>
Min: 0.0 Hz
Max: E3-04
168
E3-10
(320H)
Motor 2 Minimum Output
Frequency Voltage
Default:
<15> <25>
Min: 0.0 V
Max: 255.0 V
<15>
168
E3-11
(345H)
<17>
Motor 2 Mid Output Frequency 2
Default: 0.0 Hz
<22>
Min: 0.0 Hz
Max: E3-04
168
E3-12
(346H)
<22>
Motor 2 Mid Output Frequency
Voltage 2
Default: 0.0 V
Min: 0.0 V
Max: 255.0 V
<15>
168
E3-13
(347H)
Motor 2 Base Voltage
Default: 0.0 V
Min: 0.0 V
Max: 255.0 V
<15>
168
<15> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<17> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
<22> Parameter ignored when E3-11 (Motor 2 Mid Output Frequency 2) and E3-12 (Motor 2 Mid Output Frequency Voltage 2) are set to 0.
<25> Default setting is determined by the control mode for motor 2 (E3-01).
No.(Addr.) Name Description Setting Page
E4-01
(321H)
Motor 2 Rated Current
Sets the full load current for motor 2. Automatically set during Auto-Tuning.
Default:
<24>
Min: 10% of drive rated
current
Max: 200% of drive
rated current
<18>
169
E4-02
(322H)
Motor 2 Rated Slip
Sets the rated slip for motor 2. Automatically set during Auto-Tuning.
Default:
<24>
Min: 0.00 Hz
Max: 20.00 Hz
169
E4-03
(323H)
Motor 2 Rated No-Load Current
Sets the no-load current for motor 2. Automatically set during Auto-Tuning.
Default:
<24>
Min: 0 A
Max: E4-01
<18>
169
E4-04
(324H)
Motor 2 Motor Poles
Sets the number of poles of motor 2. Automatically set during Auto-Tuning.
Default: 4
Min: 2
Max: 48
170
E4-05
(325H)
Motor 2 Line-to-Line Resistance
Sets the phase-to-phase resistance for motor 2. Automatically set during Auto-Tuning.
Default:
<24>
Min: 0.000 Ω
Max: 65.000 Ω
170
E4-06
(326H)
Motor 2 Leakage Inductance
Sets the voltage drop for motor 2 due to motor leakage inductance as a percentage of rated
voltage. Automatically set during Auto-Tuning.
Default:
<24>
Min: 0.0%
Max: 40.0%
170
E4-10
(340H)
Motor 2 Iron Loss
Sets the motor iron loss.
Default:
<24>
Min: 0 W
Max: 65535 W
170
E4-11
(327H)
Motor 2 Rated Power
Sets the motor rated capacity in kW. Automatically set during Auto-Tuning.
Default:
<24>
Min: 0.00 kW
Max: 650.00 kW
170
No.(Addr.) Name Description Setting Page
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
Output Voltage (V)
Frequency (Hz)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09 E3-07 E3-06 E3-11 E3-04
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV