B.3 Parameter Table
390 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
1B Program lockout
Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned to the digital operator).
Closed: Parameters can be edited and saved.
187
20 to 2F External fault
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
187
30 PID integral reset
Closed: Resets the PID control integral value.
187
31 PID integral hold
Open: Performs integral operation.
Closed: Maintains the current PID control integral value.
187
34 PID soft starter cancel
Open: PID soft starter is enabled.
Closed: Disables the PID soft starter b5-17.
187
35 PID input level selection
Closed: Inverts the PID input signal
187
40 Forward run command (2-wire sequence) Open: Stop
Closed: Forward run
Note: Cannot be set together with settings 42 or 43.
187
41 Reverse run command (2-wire sequence)
Open: Stop
Closed: Reverse run
Note: Cannot be set together with settings 42 or 43.
187
42 Run command (2-wire sequence 2)
Open: Stop
Closed: Run
Note: Cannot be set together with settings 40 or 41.
188
43 FWD/REV command (2-wire sequence 2)
Open: Forward
Closed: Reverse
Note: Determines motor direction, but does not issue a Run command. Cannot be set together with settings 40 or
41.
188
44 Offset frequency 1
Closed: Adds d7-01 to the frequency reference.
188
45 Offset frequency 2
Closed: Adds d7-02 to the frequency reference.
188
46 Offset frequency 3
Closed: Adds d7-03 to the frequency reference.
188
50 Disturb Function Cancel
Open: Disturb function output is active.
Closed: Cancels the Disturb function.
188
51 Synchronous Accel/Decel
Closed: Assigns the same accel/decel times to all motors in the line so that they reach the desired frequency at the
same time.
188
53 Energy Saving On/Off
Closed: Enables the Energy Saving function.
188
H1 Multi-Function Digital Input Selections
H1-
Setting
Function Description Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV