B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual 393
Parameter List
B
11 Fault reset command active
Closed: A command has been entered to clear a fault via the input terminals or from the serial network.
194
12 Timer output
Closed: Timer output.
194
13 Speed agree 2
Closed: When drive output frequency equals the frequency reference ±L4-04.
195
14 User-set speed agree 2
Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.
195
15 Frequency detection 3
Closed: When the drive output frequency is less than or equal to the value in L4-03 ±L4-04.
196
16 Frequency detection 4
Closed: When the output frequency is greater than or equal to the value in L4-03 ±L4-04.
196
17 Torque detection 1 (N.C.)
Open: Overtorque or undertorque has been detected.
194
18 Torque detection 2 (N.O.)
Closed: Overtorque or undertorque has been detected.
194
19 Torque detection 2 (N.C.)
Open: Overtorque or undertorque has been detected.
194
1A During reverse
Closed: Drive is running in the reverse direction.
197
1B During baseblock (N.C.)
Open: Drive has entered the baseblock state (no output voltage).
197
1C Motor 2 selection
Closed: Motor 2 is selected by a digital input (H1- = 16)
197
1D During regeneration
Closed: Motor is regenerating energy into the drive.
197
1E Restart enabled
Closed: An automatic restart is performed
197
1F Motor overload alarm (oL1)
Closed: oL1 is at 10% of its trip point or greater. An oH3 situation also triggers this alarm.
197
20 Drive overheat pre-alarm (oH)
Closed: Heatsink temperature exceeds the parameter L8-02 value.
197
2F Maintenance period
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require maintenance.
197
30 During torque limit
Closed: When the torque limit has been reached.
198
31 During speed limit
Closed: Speed limit has been reached.
198
32 During speed limit in Torque Control
Closed: Speed limit has been reached while using Torque Control.
198
33 Zero Servo complete
Closed: Zero Servo operation has finished.
198
37 During frequency output
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial Excitation is being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being performed).
198
38 Drive enabled
Closed: Multi-function input set for “Drive enable” is closed (H1- = 6A)
198
H2 Multi-Function Digital Output Settings
H2-
Setting
Function Description Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes