B.3 Parameter Table
394 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
n H3: Multi-Function Analog Inputs
39 Watt hour pulse output
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.
198
3C LOCAL/REMOTE status
Open: REMOTE
Closed: LOCAL
198
3D During Speed Search
Closed: Speed Search is being executed.
198
3E PID feedback low
Closed: PID feedback level is too low.
199
3F PID feedback high
Closed: The PID feedback level is too high.
199
4A During KEB Operation
Closed: KEB is being performed.
199
4B During Short-Circuit Braking
Closed: Short Circuit Braking is active.
199
4C During Fast Stop
Closed: A Fast Stop command has been entered from the operator or input terminals.
199
4E Braking transistor fault (rr)
Closed: The built-in dynamic braking transistor failed.
Note: This setting is not available in models CIMR-T2A0169 through 2A0415 and 4A0088 through 4A362.
199
4F Braking resistor overheat (oH)
Closed: The dynamic braking resistor has overheated.
Note: This setting is not available in models CIMR-T2A0169 through 2A0415 and 4A0088 through 4A362.
199
50 Disturb increase
Closed: Disturb waveform acceleration
Open: Disturb waveform deceleration
199
51 During Disturb output
Closed: Disturb waveform is active
Open: Disturb waveform is not being output
199
52 Uv during KEB
Closed: DC bus voltage has fallen below L2-05 during KEB
199
60 Internal cooling fan alarm
Closed: Internal cooling fan alarm
199
61 Rotor position detection complete
Closed: Drive has successfully detected the rotor position of the PM motor.
199
100 to 161 Function 0 to 61 with inverse output
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1 to reverse the output signal of that specific function.
199
No.(Addr.) Name Description Setting Page
H3-01
(410H)
Terminal A1 Signal Level
Selection
0: 0 to 10 V
1: –10 to 10 V
Default: 0
Min: 0
Max: 1
201
H3-02
(434H)
Terminal A1 Function Selection
Sets the function of terminal A1.
Default: 0
Min: 0
Max: 41
201
H3-03
(411H)
Terminal A1 Gain Setting
Sets the level of the input value selected in H3-02 when 10 V is input at terminal A1.
Default: 100.0%
Min: -999.9%
Max: 999.9%
201
H3-04
(412H)
Terminal A1 Bias Setting
Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1.
Default: 0.0%
Min: -999.9%
Max: 999.9%
201
H2 Multi-Function Digital Output Settings
H2-
Setting
Function Description Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes
All Modes
All Modes

Table of Contents

Related product manuals