B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual 401
Parameter List
B
n L5: Fault Restart
n L6: Torque Detection
L4-08
(47FH)
Frequency Agree Condition
Selection
Sets whether a frequency agree situation should be determined by the soft starter output
frequency or by the estimated speed of the motor.
0: Use the soft starter output frequency to determine frequency agree
1: Use the motor speed to determine frequency agree
Default: 1
Min: 0
Max: 1
224
<12> The setting range depends on the control mode selected for the drive. The setting range is 0.0 to 100.0% in AOLV/PM and CLV/PM.
<13> The setting range depends on the control mode selected for the drive. The setting range is 0.0 to 40.0% in AOLV/PM and CLV/PM.
<14> The setting range depends on the control mode selected for the drive. The setting range is –100.0 to 100.0% in AOLV/PM and CLV/PM.
<34> Default setting is determined by the control mode (A1-02).
No. (Addr.) Name Description Setting Page
L5-01
(49EH)
Number of Auto Restart Attempts
Sets the number of times the drive may attempt to restart after the following faults occur: GF,
LF, oC, ov, PF, rH, rr, oL1, oL2, oL3, oL4, STo, Uv1.
Default: 0 Time
Min: 0 Time
Max: 10 Times
225
L5-02
(49FH)
Auto Restart Fault Output
Operation Selection
0: Fault output not active.
1: Fault output active during restart attempt.
Default: 0
Min: 0
Max: 1
225
L5-04
(46CH)
Fault Reset Interval Time
Sets the amount of time to wait between performing fault restarts.
Default: 10.0 s
Min: 0.5 s
Max: 600.0 s
225
L5-05
(467H)
Fault Reset Operation Selection
0: Continuously attempt to restart while incrementing restart counter only at a successful
restarts (same as F7 and G7).
1: Attempt to restart with the interval time set in L5-04 and increment the restart counter with
each attempt (same V7).
Default: 0
Min: 0
Max: 1
226
No. (Addr.) Name Description Setting Page
L6-01
(4A1H)
Torque Detection Selection 1
0: Disabled
1: oL3 detection only active during speed agree, operation continues after detection
2: oL3 detection always active during run, operation continues after detection
3: oL3 detection only active during speed agree, output shuts down on an oL3 fault
4: oL3 detection always active during run, output shuts down on an oL3 fault
5: UL3 detection only active during speed agree, operation continues after detection
6: UL3 detection always active during run, operation continues after detection
7: UL3 detection only active during speed agree, output shuts down on an oL3 fault
8: UL3 detection always active during run, output shuts down on an oL3 fault
Default: 0
Min: 0
Max: 8
227
L6-02
(4A2H)
Torque Detection Level 1
Sets the overtorque and undertorque detection level.
Default: 150%
Min: 0%
Max: 300%
227
L6-03
(4A3H)
Torque Detection Time 1
Sets the time an overtorque or undertorque condition must exist to trigger torque detection 1.
Default: 0.1 s
Min: 0.0 s
Max: 10.0 s
227
L6-04
(4A4H)
Torque Detection Selection 2
0: Disabled
1: oL4 detection only active during speed agree, operation continues after detection
2: oL4 detection always active during run, operation continues after detection
3: oL4 detection only active during speed agree, output shuts down on an oL4 fault
4: oL4 detection always active during run, output shuts down on an oL4 fault
5: UL4 detection only active during speed agree, operation continues after detection
6: UL4 detection always active during run, operation continues after detection
7: UL4 detection only active during speed agree, output shuts down on an oL4 fault
8: UL4 detection always active during run, output shuts down on an oL4 fault
Default: 0
Min: 0
Max: 8
227
L6-05
(4A5H)
Torque Detection Level 2
Sets the overtorque and undertorque detection level.
Default: 150%
Min: 0%
Max: 300%
227
L6-06
(4A6H)
Torque Detection Time 2
Sets the time an overtorque or undertorque condition must exist to trigger torque detection 2.
Default: 0.1 s
Min: 0.0 s
Max: 10.0 s
227
No. (Addr.) Name Description Setting Page
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes