D.3 UL Standards
484 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum
allowable temperature of 75°C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 40°C.
4A0044
R/L1, S/L2, T/L3 16 16 to 25
M6
4 to 6
(35.4 to 53.1)
U/T1, V/T2, W/T3 16 16 to 25
–, +1, +2 – 16 to 25
B1, B2 – 6 to 10 M5
2 to 2.5
(17.7 to 22.1)
16 10 to 16 M6
4 to 6
(35.4 to 53.1)
4A0058
<1>
R/L1, S/L2, T/L3 16 10 to 16
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 16 10 to 16
–, +1 – 16 to 35
B1, B2 – 10 to 16
16 10 to 16
4A0072
<1>
R/L1, S/L2, T/L3 16 16 to 25
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 25 16 to 25
–, +1 – 25 to 35
B1, B2 – 16 to 25
16 16 to 25
4A0088
<1>
R/L1, S/L2, T/L3 25 16 to 50
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 25 25 to 50
–, +1 – 25 to 50
+3 – 16 to 50
16 16 to 25
4A0103
<1>
R/L1, S/L2, T/L3 35 25 to 50
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 35 25 to 50
–, +1 – 25 to 50
+3 – 25 to 50
16 16 to 25
4A0139
<1>
R/L1, S/L2, T/L3 50 35 to 95
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 50 35 to 95
–, +1 – 50 to 95
+3 – 25 to 95
25 25
4A0165
<1>
R/L1, S/L2, T/L3 70 50 to 95
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 70 70 to 95
–,+1 – 35 to 95
+3 – 50 to 95
35 25 to 35
4A0208
<1>
R/L1, S/L2, T/L3 95 35 to 95
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 95 35 to 95
–, +1 – 35 to 150
+3 – 25 to 70
50 50 to 150
4A0250
<1>
R/L1, S/L2, T/L3 120 95 to 300
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 120 95 to 300
–, +1 – 70 to 300
+3 – 35 to 300
70 70 to 240
4A0296
<1>
R/L1, S/L2, T/L3 185 95 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 185 95 to 300
–, +1 – 70 to 300
+3 – 35 to 300 M10
18 to 23
(159 to 204)
95 95 to 240 M12
32 to 40
(283 to 354)
4A0362
<1>
R/L1, S/L2, T/L3 240 95 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 240 95 to 300
–, +1 – 95 to 300
+3 – 70 to 300 M10
18 to 23
(159 to 204)
120 120 to 240 M12
32 to 40
(283 to 354)
<1> Drive models CIMR-T4A0058 to 4A0362 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
Model
CIMR-T
Terminal
Recommended Gauge
mm
2
Applicable
Gauge
mm
2
Screw
Size
Tightening
Torque
Nxm (lb.in.)