Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / uint16Main status word of the drive.
The bit assignments are described on page 617. The related
control word and state diagram are presented on pages
615 and 618.
Note: In fieldbus control, this parameter value is not exactly
the same as the status word that the drive sends to the
PLC. See parameter 50.12 FBA A debug mode.
This parameter is read-only.
Main status word6.11
- / uint16Drive status word 1.
This parameter is read-only.
Drive status word 16.16
1 = Both run enable (see par. 20.12) and start enable
(20.19) signals are present, and Safe torque off has not
been activated.
Note:
In I/O or local control, clearing this bit makes the drive
enter the SWITCH-ON INHIBITED state. For further
information, see 617.
This bit is not affected by the presence of a fault.
Enabledb0
1 = Start inhibited. See parameters 6.18 and 6.25 for the
source of the inhibiting signal.
Inhibitedb1
1 = DC circuit has been charged. If present, the DC switch
is closed, and charging switch is open.
0 = Charging not complete. If the inverter unit is not
equipped with a DC switch (option +F286), check setting
of 95.9.
DC chargedb2
1 = Drive is ready to receive a start commandReady to startb3
1 = Drive is ready to follow given referenceFollowing referenceb4
1 = Drive has been startedStartedb5
1 = Drive is modulating (output stage is being controlled)Modulatingb6
1 = Any operating limit (speed, torque, etc.) is activeLimitingb7
1 = Drive is in local controlLocal controlb8
1 = Drive is in network control. See Terms and
abbreviations (page 17).
Network controlb9
1 = Control location EXT1 activeExt1 activeb10
1 = Control location EXT2 activeExt2 activeb11
Reservedb12
1 = Start requested
Note: At the time of publishing, a start request from the
control panel does not activate this bit if any start-inhibiting
condition (see bit 1) is present.
Start requestb13
Reservedb14…15
1 = 10000h…FFFFh
- / uint16Drive status word 2.
This parameter is read-only.
Drive status word 26.17
156 Parameters