Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
3
Drive generates an A7CA DDCS controller comm loss
warning and sets the speed to the speed defined by
parameter 22.41 Speed ref safe (or 28.41 Frequency ref
safe when frequency reference is being used). This only
occurs if control is expected from the external controller,
or if supervision is forced using parameter 60.65 DDCS
controller comm supervision force.
WARNING!
Make sure that it is safe to continue operation in
case of a communication break.
Speed ref safe
4
Drive trips on 7581 DDCS controller comm loss. This
occurs even though no control is expected from the external
controller.
Fault always
5
Drive generates an A7CA DDCS controller comm loss
warning. This only occurs if control is expected from the
external controller, or if supervision is forced using
parameter 60.65 DDCS controller comm supervision force.
WARNING!
Make sure that it is safe to continue operation in
case of a communication break.
Warning
Auto / uint16Selects the type and scaling of reference 1 received from
the external controller. The resulting value is shown by
3.11 DDCS controller ref 1.
DDCS controller ref1
type
60.60
0Type and scaling are chosen automatically according to
which reference chain (see settings Torque, Speed,
Frequency) the incoming reference is connected to. If the
reference is not connected to any chain, no scaling is
applied (as with setting Transparent).
Auto
1No scaling is applied.Transparent
2Generic reference with a scaling of 100 = 1 (ie. integer and
two decimals).
General
3
The scaling is defined by parameter 46.3 Torque scaling.
Torque
4
The scaling is defined by parameter 46.1 Speed scaling.
Speed
5
The scaling is defined by parameter 46.2 Frequency
scaling.
Frequency
Auto / uint16Selects the type and scaling of reference 2 received from
the external controller. The resulting value is shown by
3.12 DDCS controller ref 2.
For the selections, see parameter 60.60 DDCS controller
ref1 type.
DDCS controller ref2
type
60.61
Auto / uint16Selects the type/source and scaling of actual value ACT1
transmitted to the external controller.
DDCS controller act1
type
60.62
454 Parameters