Rockwell Automation Publication 1769-UM022C-EN-P - June 2018 21
Chapter 2
Install the Controller
Precautions
Topic Page
Precautions 21
Compact GuardLogix 5370 Controller Parts 23
Install the Secure Digital (SD) Card 24
Plan the System 25
Assemble the System 26
Mount the System 27
Mount the System 27
Connect Power to the Control System 31
Connect to the Controller via a USB Cable 31
Connect the Controller to an EtherNet/IP Network 32
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in
IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is supplied as open-type equipment. It must be mounted
within an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent
personal injury resulting from accessibility to live parts. The enclosure must
have suitable flame-retardant properties to prevent or minimize the spread of
flame, complying with a flame spread rating of 5VA or be approved for the
application if nonmetallic. The interior of the enclosure must be accessible
only by the use of a tool. Subsequent sections of this publication may contain
additional information regarding specific enclosure type ratings that are
required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1
, for additional installation requirements
• NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of
protection provided by different types of enclosures