Rockwell Automation Publication 1769-UM022C-EN-P - June 2018 33
Chapter 3
Complete the Controller Setup
To complete the tasks that are described in this chapter, you must have the
following software installed on your computer.
•RSLinx® Classic
Studio 5000® environment
BOOTP-DHCP server (installed with RSLinx Classic)
ControlFLASH™ (installed with Studio 5000 environment)
Compact GuardLogix® 5370 controllers require a network Internet Protocol
(IP) address to operate on an EtherNet/IP
network.
Set the IP Address
The IP address uniquely identifies the controller. The IP address is in the form
xxx.xxx.xxx.xxx where each xxx is a number from 000…254 with some
exceptions for reserved values. These numbers are examples of reserved values
you cannot use:
000.xxx.xxx.xxx
127.xxx.xxx.xxx
224 to 255.xxx.xxx.xxx
Some other values are reserved based on an application-by-application basis.
Topic Page
Set the IP Address 33
Change the IP Address 42
Load Controller Firmware 45
Select the Operating Mode of the Controller 53

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Compact GuardLogix 5370 and is the answer not in the manual?

Allen-Bradley Compact GuardLogix 5370 Specifications

General IconGeneral
BrandAllen-Bradley
ModelCompact GuardLogix 5370
CategoryController
LanguageEnglish

Related product manuals