Introduction and Technical Data 23
Control Circuits: Fully isolated from po w er circuit.
Control Action: Advanced PI with fully adaptive current loops for optimum dynamic performance.
Self-Tuning Current Loop utilising " Autotune " algorithm.
Adjustable speed PI with integral defeat.
Speed Control: By Armature Voltage feedback with IR compensation.
By encoder feedback or analogue tachogenerator.
By a combination of encoder feedback and analogue tachogenerator or A VF.
Speed range 100 to 1 typical with tachogenerator feedback.
Steady State A ccuracy: 0.1 % Analogue Tachogenerator Feedback. (subject to tachogenerator)
2 % Armature Voltage Feedback
0.01 % Encoder only, Encoder + tacho, encoder + A VF – (With digital reference)
Protection: Interline device net works. High energy MOV'S.
Overcurrent (instantaneous). Overcurrent 150 % for 25s.
Field failure. Tacho failure. (With auto A V F back-up option).
Motor over-temperature. Thyristor Stack over-temperature.
Thyristor " Trigger" failure. Zero-speed detection.
Standstill logic. Stall protection.
Diagnostics: With first fault latch, automatic display and power off memory.
Diagnostic monitoring of all parameters in engineering and/or % units.
Full diagnostic information available on RS232 using PL PILOT graphical tool.
Digital I/O logic status plus automatic default % diagnostic summary windows
Temperature: 0-40 C ambient operating temperature. (35C for PL/X 900 and PL/X980)
Derate by 1 % per Deg C above 40C up to 50 C max. storage- + 5 C - + 55C
Protect from direct sunlight. Ensure dry, corrosive free environment.
Humidity: 85 % Relative humidity maximum.
Note: - Relative humidity is temperature dependent, do not allo w condensation.
Atmosphere: Non-flammable, non-condensing. Pollution Degree: 2, Installation cat: 3
Altitude: Derate by 1 % per 100 Metres above 1000 Metres
Short circuit-rating: Suitable for use on a circuit capable of delivering not more than
5000 A PL/X5-30, 10,000 A PL/X 40-145, 18 00 0 A PL/X185-265
RMS symmetrical amperes, 480 Volts A C maximum, when protected
by Ar class fuses. (See fuse table). See also PL/X 650-9 80 manual.
Field output modes: Constant current, Constant voltage, Automatic weakening
Delayed quenching after stop command to allo w dynamic braking
Economy mode to leave field excited at lo w level to prevent motor cooling
Field supply inputs independent from armature supply inputs
Special features: Field weakening Motorised pot simulator Connection Conflict Checker
Dual motor swap Spindle orientation 3 Total Instrument Recipe pages
PC configuration and monitoring tool Family of remote interface units.
Application blocks: Centre winding, 2 Summers, Batch counter, Latch, 8 Multi-function, Preset Speed, 2
PIDs, Parameter profiler, 4 Comparators, 4 Changeover s witches, Delay timer, Filters.
Serial comms RS232 port, ANSI-X 3.28-2.5-B I multi-drop. Fieldbus options. Profibus, Devicenet.
Ethernet using Drive web technology.