234 Record of modifications
16.2 Record of bug fixes
See Apps manual for bug fixes relevant to applications blocks topics.
Manual
Version
Function with Bug Comments Paragraph
reference
Date Soft ware
version
2.0 3 Refer to supplier 2.X X
3.0 1 Refer to supplier
4.0 0 No bugs recorded in main drive
blocks
Sept
200 0
4.0 1
4.0 3 JO G/SLA C K RA MP
67)SPD/CUR RF3 RA TIO
Did not unlatch at the end of SLA CK operation. No w OK
Did not scale correctly. No w OK
6.3.6
6.6.7
Feb
200 1
4.0 3
4.0 5 No bugs recorded in main drive
blocks
July 2 001 4.04
4.0 5
5.0 1 D A T A CORRUPTION possible if
control supply removed during active
ASCII C O MMS transmission.
This w as possible when using PL PILO T if PILOT left
running and control supply removed. No w OK.
9.1.1 Mar
200 2
5.0 1
5.0 1 DOP3 gives unwanted low to high
transitions if A SCII C O MMS active.
DOP3 is default output of DRIVE HE ALTHY FLA G so is
normally high, and causes trip on first lo w , w hich masks
bug. Bug w as more of a nuisance if DOP3 re-configured
for ne w task which requires normally low output AND
ASCII C O MMS w as active. No w OK.
13.7 Mar
200 2
5.0 1
5.0 2 No bugs recorded in main drive
blocks
July
02
5.0 2
5.1 2 No bugs recorded in main drive
blocks
Jan 03 5.1 2
5.1 4 UIP3 malfunction w hen 8)M A X
T A CHO VOLTS set below + /-30V.
SUM MER1 and SUMMER2 subtotals
description in manual and G ET FRO M
list transposed.
64)SPD/CUR REF 3 M ON changed to
64)SPEED REF 3 MON.
18)RA TED ARM V OLTS feedback
scaling assumes value of 16 0 V
internally for entered values below
160 V. 126)ARM VOLTS M ON
assumed entered value.
Now O K.
Now O K. Still transposed in PL pilot version up to 4.05
Monitoring function inhibited in speed bypass mode.
Now O K.
13.3.1
Apps man.
6.6.4
6.1.15
Sep 04 5.1 4
5.1 4 1 0 Amp, 20 A mp, 50 A mp Field
options. Display reading made
compatible with these options
For customers who require higher field current options
the displayed parameters now agree with the increased
capability.
6.1.4 July
08
5.1 6
5.1 4 Field current loop becomes in-
operative for 4)RATED FIELD AMPS
set above 31.25% of max rating.
Bug fixed for software version 5.1 7
and above.
Work round. For field currents above 3 1.2 5 % of model
rating use 1 00)FIELD V OLTS OP % to set field current to
the correct level. For field weakening applications
Upgrade soft ware.
6.1.4
6.9.3
Oct 0 8 5.1 6
5.1 5 Fixed above bug with field current All units traced and memo issued to users. Oct 0 8 5.1 7
17 Changes to pr oduct since manual publication
Any ne w features that affect the existing functioning of the unit, that have occurred since the publication of
the manual, will be recorded here using an attached page.