CHA NGE PARA METERS 87
The following conditions must be true for the main contactor to be energised.
1) All alarms A ND supply synchronisation healthy. ( 699)RE ADY FLAG ).
2) CSTOP at 24V. Note. The CSTOP must be high for at least 50mS prior to START going high.
3) Start OR Jog high.
When the contactor has energised, the drive will run if
RUN input is high AND if enabled, the ZERO INTERLO CK is satisfied.
The contactor will de-energise after approximately 100 milliseconds if
699)RE A DY FLA G goes lo w OR CSTOP goes lo w
If the zero interlock is enabled and requests a non-run action, then the contactor will energise for
approximately 2 seconds but no current will flo w. The contactor will drop out if the zero reference interlock
condition is not satisfied within approximately 2 seconds. The display wi ll show C ONTA CTOR LO CK OUT.
The contactor will de-energise if ST ART and JOG are both low. In this case the time taken for the contactor
to de-energise depends on the ST OP MO DE RA MP when stopping from a running mode, or JOG/SLA C K
RA MP when stopping from a jog mode.
Note flags on hidden PINs, 689)IN JO G FLAG, 698)HEALTHY FLA G, 699)RE A DY FLAG,
714)IN SLA C K FLAG, 720)SYSTEM RESET pulse.
6.5.1.2 Speed profile w hen stopping
6.5.1.3 Contactor drop out
If ST ART or JOG goes high during the 60)DROP-OUT DELA Y time, then the contactor stays energised and
the drive will restart immediately. The 60)DROP-OUT DELAY timer will be reset to time zero. This allo ws
jogging without the contactor dropping in and out.
Speed reference
Start goes
low
SPEED DEMA ND
Stop ramp time is
set by PIN 56
Motor speed if current
demand stays at limit
Motor speed if drive is
not able to regenerate,
or if either the CSTOP or
RUN line go LO W
Motor speed follow s do wn
ramp providing current
de
m
a
n
d
does
n
ot
limi
t
TIME A XIS
Speed reference
Start goes
low
Contactor drops out at
this time if it has not
already dropped out.
E. g Motor unable to
sl o w do w n fast enough.
Contactor drops
out at this time
providing the
speed follo ws
the do w n ramp
Stop time limit PIN 57
Delay timer
starts now
Drop out Delay
time PIN 60
Motor will coast if
live delay mode PIN
58
i
s
D
I
S
ABLE
D
SPEED DEMA ND
Stop ramp time is
set by PIN 56
Drop out speed
set by PIN 59
MO T OR SPEED
follo w ing ramp
TIME A XIS