EasyManua.ls Logo

Bardac PLX - 13.13 CONFIGURATION; DRIVE PERSONALITY; 13.13.1 DRIVE PERSONALITY; PASSIVE MOTOR SET

Default Icon
235 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
196 CONFIGURA TION
There are many advantages to providing FIELDBUS configuration on the PL/X itself, rather than relying on the
host system to control the configuration.
1) Any PL/X parameter is available for selection as a source by each one of 8 GET FROMs (1 w ord each), +
one group of 8 w ay bit packed logic value GET FROMs (1 word).
Any legal PL/X parameter is available for selection as a target by each one of 8 G OTOs (1 word each), +
one group of 8 w ay bit packed logic value GOT Os (1 word).
2) The PL/X GO TO conflict checker automatically checks to see if the GOTO connections are accidently
configured by the user to another PL/X G OT O.
3) Reconfiguring the FIELDBUS for any PL/X, without stopping the master or other PL/X units, is possible.
4) The FIELDBUS configuration for each PL/X is held within the unit itself and is also retained in the
parameter exchange file. 3 FIELDBUS configurations can be saved in each PL/X by using the 3 recipe pages.
13.13 CONFIGURATION / DRIVE PERSONALITY
PIN numbers used 677 to 680
This menu is used to modify or monitor various
aspects of the PL/X personality.
1) PASSIVE MOTOR SET contains all the
windo ws used by the CH ANGE PARA METERS
reduced menu in ascending PIN order to set the
passive reduced values for motor 1 or 2.
2) RECIPE PAGE is used to set the target
page for a PARA METER S A VE operation. There are 3
separate pages that each allo w a total instrument to
be stored. To re-call any page requires the
appropriate power up reset choice.
3) MAX CUR RESPONSE allo ws a super fast
current response to be enabled.
4) ID ABCXRxxx MON, is used by the
unit suppliers to identify the pow er chassis and is not
intended to be used for any other purpose. A binary code is displayed.
5) Iarm BURDEN OHMS is used, along with the actual burden, to derate the model armature current.
13.13.1 DRIVE PERSONALITY / PA SSIVE MOTOR SET
See 6.1.17 C ALIBRA TION / Motor 1 or 2 select PIN 20. The passive motor set parameters are the ones
used in the REDUCED Menu. The PASSIVE MOT OR SET is also useful for a rapid revie w of the alterable
parameters in the CH A NGE PARA METERS reduced menu, or setting these parameters for a second system
while the existing system is running a motor. See 11.1 DISPLA Y FUNC TIONS / Reduced menu enable.
The power up default function (See 5.1.3 Restoring the drive parameters to the default condition) is applied
to both sets of values. How ever each set preserves its prevailing C ALIBRA TIO N parameters. See chapter 15.
PIN number tables to identify the members of the CHANGE PARA METERS reduced menu.
CONFIGURATION 2
DRIVE PERSON ALITY 3
DRIVE PERSON ALITY 3
680)Iarm BURDEN OHMS
DRIVE PERSON ALITY 3
PASSIVE M OT OR SET 4
DRIVE PERSON ALITY 3
678)M A X CUR RESPONSE
DRIVE PERSON ALITY 3
679)ID A BC XRxxx MO N
DRIVE PERSON ALITY 3
677)RECIPE PA GE
DRIVE PERSON ALITY 3
PASSIVE M OT OR SET 4
PASSIVE M OT OR SET 4
PIN)Description of parameter
PARA METER RANGE PIN
PASSIVE M OT OR SET Reduced menu parameters X X X
Allo ws vie wing and alteration
of the passive reduced menu.

Table of Contents