Cisco ONS 15454 Troubleshooting Guide, R8.5
November 2009
Chapter 2 Alarm Troubleshooting
2.7.329 PWR-FAIL-RET-A
The Equipment Power Failure at Connector B alarm occurs when there is no power supply from the main
power connector to the equipment. This alarm occurs on the electrical interface assemblies (EIA),
15454_MRC-12 Multirate card, MRC-2.5G-4 Multirate card, OC192SR1/STM64IO Short Reach and
OC192/STM64 Any Reach cards (also known as OC192-XFP in CTC), OC12 IR/STM4 SH 1310-4 card,
OC3 IR/STM1 SH 1310-8 card or TCC2/TCC2P.
Warning
The power supply circuitry for the equipment can constitute an energy hazard. Before you install or
replace the equipment, remove all jewelry (including rings, necklaces, and watches). Metal objects
can come into contact with exposed power supply wiring or circuitry inside the DSLAM equipment.
This could cause the metal objects to heat up and cause serious burns or weld the metal object to the
equipment.
Statement 207
Clear the PWR-FAIL-B Alarm
Step 1 Complete the “Clear the PWR-FAIL-A Alarm” procedure on page 2-200.
Step 2 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC 1 800 553-2447.
2.7.329 PWR-FAIL-RET-A
Default Severity: Minor (MN), Non-Service-Affecting (NSA)
SONET Logical Object: EQPT
The Equipment Power Failure at Connector A alarm occurs when there is no power supplied to the
backup power connector on the shelf. This alarm occurs on the electrical interface assemblies (EIA),
15454_MRC-12 Multirate card, MRC-2.5G-4 Multirate card, OC192SR1/STM64IO Short Reach and
OC192/STM64 Any Reach cards (also known as OC192-XFP in CTC), OC12 IR/STM4 SH 1310-4 card,
OC3 IR/STM1 SH 1310-8 card or TCC2/TCC2P.
Clear the PWR-FAIL-RET-A Alarm
Step 1 Complete the “Clear the PWR-FAIL-A Alarm” procedure on page 2-200.
Step 2 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC 1 800 553-2447.
2.7.330 PWR-FAIL-RET-B
Default Severity: Minor (MN), Non-Service-Affecting (NSA)
SONET Logical Object: EQPT