Chapter 11 Summary of Parameter Settings
MH300
Pr. Parameter Name Setting Range Default
02-37
Output terminal of
extension card (MO11)
or
(RY11)
9: Drive is ready
0
10: Low voltage warning (Lv) (Pr.06-00)
11: Malfunction indication
02-38
Output terminal of
extension card (MO12) or
(RY12)
13: Over-heat warning (Pr.06-15)
14: Software brake signal indication (Pr.07-00)
0
15: PID feedback error (Pr.08-13, 08-14)
16: Slip error (oSL)
17: Count value reached; does not return to 0 (Pr.02-20)
18: Count value reached; returns to 0 (Pr.02-19)
19: External interrupt B.B. input (Base Block)
20: Warning output
21: Over-voltage
22: Over-current stall prevention
23: Over-voltage stall prevention
24: Operation source
25: Forward command
26: Reverse command
29: Output when frequency ≥ Pr.02-34
30: Output when frequency < Pr.02-34
31: Y-connection for the motor coil
32: Δ-connection for the motor coil
33: Zero speed (actual output frequency)
34: Zero speed including STOP (actual output frequency)
35: Error output selection 1 (Pr.06-23)
36: Error output selection 2 (Pr.06-24)
37: Error output selection 3 (Pr.06-25)
38: Error output selection 4 (Pr.06-26)
39: Position reached (Pr.10-19)
40: Speed reached (including STOP)
42: Crane function
43: Motor actual speed detection
44: Low current output (use with Pr.06-71–06-73)
45: UVW output electromagnetic valve switch
46: Outputs master dEb action
49: Homing action completed
50: Output control for CANopen
51: Output control for RS-485
52: Output control for communication cards
66: SO output logic A
67: Analog input level reached