Chapter 12 Description of Parameter Settings
MH300
12.1-02-22
02-21
Digital Output Gain (DFM)
Default: 1
Settings 1–55
Sets the signal for the digital output terminals (DFM-DCM) and the digital frequency output (pulse,
work period = 50 %). The output pulse per second = output frequency x Pr.02-21.
02-22
Desired Frequency Reached 1
Default: 60.00 / 50.00
Settings 0.00599.00 Hz
02-23
The width of the desired frequency reached 1
Default: 2.00
Settings 0.00599.00 Hz
02-24
Desired Frequency Reached 2
Default: 60.00 / 50.00
Settings 0.00599.00 Hz
02-25
The width of the desired frequency reached 2
Default: 2.00
Settings 0.00599.00 Hz
Once the output speed (frequency) reaches the desired speed (frequency), if the corresponding
multi-function output terminal is set to 3 or 4 (Pr.02-13, Pr.02-16, and Pr.02-17), this multi-
function output terminal isclosed”.