Chapter 12 Description of Parameter Settings
MH300
.1-09-7
Other DeviceNet Speed Settings (for DeviceNet)
Default: 0
Settings 0: Disable:
In this mode, baud rate must be 125 Kbps, 250 Kbps, 500 Kbps, or 1 Mbps
in the standard DeviceNet speed.
1: Enable:
In this mode, DeviceNet baud rate must be same as that for CANopen baud
rate (0–8).
Use this parameter with Pr.09-71.
0: The baud rate can only be set to 125 Kbps, 250 Kbps and 500 Kbps as a standard DeviceNet
speed.
1: The DeviceNet communication rate can be the same as that for CANopen (setting 0–8).
Communication Card IP Configuration (for EtherNet)
Default: 0
Settings 0: Static IP
1: Dynamic IP (DHCP)
0: Set the IP address manually.
1: IP address is automatically set by the host controller.
Communication Card IP Address 1 (for EtherNet)
Communication Card IP Address 2 (for EtherNet)
Communication Card IP Address 3 (for EtherNet)
Communication Card IP Address 4 (for EtherNet)
Default: 0
Settings 0–255
Use Pr.09-76–09-79 with a communication card.
Communication Card Address Mask 1 (for EtherNet)
Communication Card Address Mask 2 (for EtherNet)
Communication Card Address Mask 3 (for EtherNet)
Communication Card Address Mask 4 (for EtherNet)
Default: 0
Settings 0–255
Communication Card Gateway Address 1 (for EtherNet)
Communication Card Gateway Address 2 (for EtherNet)
Communication Card Gateway Address 3 (for EtherNet)
Communication Card Gateway Address 4 (for EtherNet)
Default: 0