Chapter 3: Certify Twisted Pair Cabling
Settings for Twisted Pair Tests
87
Outlet
Configuration
The Outlet Configuration specifies which wire pairs are
tested and which wire numbers the wire map shows for the
pairs. See Figures 28 and 29.
To see the wire map for a configuration, tap Outlet
Configuration, tap the configuration name on the OUTLET
CONFIG screen, then tap SAMPLE.
To select a configuration, tap a name on the OUTLET
CONFIG screen, then tap USE SELECTED.
Note
The OUTLET CONFIG screen shows only the
configurations that are applicable to the
selected Test Limit.
To make a custom outlet configuration, tap CUSTOM on
the OUTLET CONFIG screen, then tap MANAGE, then tap
Create. See Chapter 19 for details.
AC Wire Map
The AC Wire Map test lets you do tests on links connected
through midspan PoE (Power over Ethernet) devices. See
Chapter 4.
When the AC Wire Map test is on, this icon shows on the
home screen:
Notes
Always turn off the AC wire map test when you
will not do tests through a PoE device. The AC
wire map test increases the time for an
Autotest. It also disables the resistance and
shield continuity tests.
AC Wire Map is not available when a DSX-8000
module is installed. The DSX-8000 modules do
not support the AC wire map test.