Versiv Series Cabling Certification Product Family
Technical Reference Handbook
262
1-5 On the SET REFERENCE screen, tap RUN WIZARD.
Notes
To only set the reference, and not measure the
loss of your test reference cords, tap SKIP WIZARD
on the SET REFERENCE screen.
Fluke Networks recommends that you measure
the loss of your test reference cords each time you
set the reference.
1-6 Make the connections to set the reference, as shown on the
screen and in Figure 111, then tap NEXT to see the completed
connections.
Notes
The SET REFERENCE screen shows reference
connections for the selected reference method.
Figure 111 shows connections for a 1 Jumper
reference.
When you set the reference, align the testers as
shown in Figure 111 to keep the fibers as straight
as possible.
1-7 To enter the length of the test reference cords you will add to
connect to the link, tap TRC LENGTH on the SET REFERENCE
screen. The length you enter does not change the test results.
The tester saves the length with the results to meet TIA
reporting requirements.
1-8 Tap SET REFERENCE.
If reference values are unacceptable, you can use the
FiberInspector probe to inspect connectors. To turn on the
probe, press the button on the probe. To go back to the
reference screen, tap .
1-9 If you did not use the connection wizard, go to step 3.