Versiv Series Cabling Certification Product Family
Technical Reference Handbook
370
8 Clean and inspect the connector for End 1 of the link that has
the next ID in the set.
9 Connect the tester to End 1 of the next link, then tap TEST or
press .
10 Repeat steps 8 and 9 for all IDs in the set.
11 Press , then tap the Next ID panel.
12 On the CHANGE ID screen, tap the End 1/End 2 control at the
top of the screen to make it show End 2. In the list under IDs
Untested, the tester highlights the first ID that does not include
results for End 2. This should be the first ID in the set.
13 Tap DONE on the CHANGE ID screen.
14 Clean and inspect the connector for End 2 of the link that has
the first ID in the set.
15 Connect the tester to End 2 of the link, then tap TEST or press
.
16 Clean and inspect the connector for End 2 of the link that has
the next ID in the set.
17 Connect the tester to End 2 of the next link, then tap TEST or
press . For a description of bi-directional test results, see
“Averaged Bi-directional Results” on page 388.
18 Repeat steps 16 and 17 for all IDs in the set.