Versiv Series Cabling Certification Product Family
Technical Reference Handbook
428
combined loss, tap the event that causes the hidden event. ().
The tester does not show loss measurements for hidden events.
See HIDDEN on page 435.
: The event is hidden by a previous event. The reflectance of
the event exceeds the limit. This icon shows only when the test
limit has a limit for reflectance.
The cause of the hidden event. The loss of the second
connector is hidden in the attenuation dead zone of the first
connector.
When more than one button shows at the bottom of the
screen, the tester highlights one in yellow to recommend
which one to tap. See “Buttons to Do Tests and Save Results”
on page 61.
The fiber type and test limit the tester used for the test, and
the ID the tester will use for the next results that you save.
When a test is completed, the window shows information for
the event that has the worst measurement. The information
windows show the worst results of the wavelengths used for
the test.
If the window border is green, the measurements for the event
do not exceed the limits.
If the window border is red, a measurement exceeds the limits.
If the window border is blue, the tester does not give a pass or
fail result to the event because it cannot do a full analysis of the
event. This occurs for OTDR Port, Hidden, and End events. This
occurs for all events if you use the Document Only test limit
because Document Only does not have values for limits.
When you use a test limit that has a reflectance limit, Hidden
events show a fail status if their reflectance exceeds the limit.