4-8 SPARC Enterprise M4000/M5000 Servers Service Manual December 2010
The replacefru command automatically tests the status of the component after the
remove and replace is finished.
Note The display may vary depending on the XCP version.
When the tests are complete the program returns to the original menu. Select cancel
to return to the XSCF Shell prompt.
Refer to the replacefru man page for more information.
EXAMPLE 4-2 replacefru command status
Diagnostic tests of FAN_A#0 is started.
[This operation may take up to 2 minute(s)]
(progress scale reported in seconds)
0..... 30..... 60..... 90.....done
----------------------------------------------------------------
Maintenance/Replacement Menu
Status of the replaced unit.
FRU Status
------------- --------
FAN_A#0 Normal
----------------------------------------------------------------
The replacement of FAN_A#0 has completed, normally.[f:finish] :f
----------------------------------------------------------------
Maintenance/Replacement Menu
Please select a type of FRU to be replaced.
1. FAN (Fan Unit)
2. PSU (Power Supply Unit)
----------------------------------------------------------------
Select [1,2|c:cancel] : C
XSCF>