6.1 Viewing Instantaneous Data (VIEW Screen)
101
6
The following measurement values are displayed numerically (DMM
screen).
The number of channels for which paramters are displayed depends on the
s
elected wiring configuration.
Displaying the DMM Screen (voltage, current and instantaeous power
values) [DMM]
U rms U peak+ U peak- U THD
rms voltage Voltage Waveform Peak Value
Voltage Total
Harmonic Distortion
I rms I peak+ I peak- KF/ I THD
Rms Current Current Waveform Peak Value
K Factor/ Current Total
Harmonic Distortion
P S Q PF
Active Power Apparent Power Reactive Power
Power Factor
(o
r DPF - Displace-
ment Power Factor)
Uave Iave Uunb
Rms Voltage
Channel average
Rms Current
Channel average
Voltage Unbalance
Select the screen.
(p. 96)
3 phase summa-
tion
Select KF or I THD
When 3P3W2M or 3P3W3M is selected, the active power(P1,P2,P3), reactive
power(Q1,Q2,Q3), apparent power(S1,S2,S3), and power factor(PF1,PF2,PF3) of
each channel are meaningless data. Use the total values of Psum,Qsum,Ssum,
and PFsum only. The data of each channel is used as reference data for checking
the wiring.