POTENTIAL OPERATING ISSUES
Part. No. 2400M2501_6 Touchpoint Pro
154 Technical Handbook
The Input Module cannot be
commissioned: The maximum
number of 16 Input Modules has
already been commissioned on
the system.
TPPR has a
maximum capacity of
16 Input and 32
Output Modules
If more channels than 64 inputs and 128
outputs are required an additional TPPR
system is needed. Contact your local
representative to discuss your requirements
The Output Module cannot be
commissioned: The maximum
number of 32 Output Modules
has already been commissioned
on the system.
CCB receives wrong
Test sequence for
Relay tests
The user could not be added;
invalid user name. Please
choose a different user name
and try again.
The user name must
be 4 to 20 characters
long
Please choose a user name that meets the
requirements and try again
Kill Session denied
Configuration Backup / Restore
in Progress
User has attempted
to end a session for
the PC configuration
SW while a CCB
configuration backup
or restore is in
progress
Retry after the configuration restore operation
is completed.
Check with the user at the local controller that it
is acceptable to log in from remote PC.
Kill Session denied CCB
Firmware update in Progress.
User has attempted
to end a session for
the PC configuration
SW while a CCB
firmware update is in
progress
Retry after the firmware download operation is
completed.
Check with the user at the local controller that it
is acceptable to log in from remote PC.
The controller needs a restart to
proceed further. Please power
cycle the controller and try
again.
The system is being
updated and needs a
power cycle to
continue.
Cycle the power supply off, wait 15 to 20
seconds and then power on again
System is running in test mode.
One of the three test
modes is active, and
other operations are
restricted or not
permitted
Wait until testing is complete. If necessary, exit
Test Mode to carry out the required operation.
Operation failed; Save
Calibration Failed.
TPPR was unable to
save the sensor
calibration
Please retry the operation.
Operation failed; Channel Wiring
Fault.
TPPR cannot detect
that a sensor is
connected to the
channel or it has
detected incorrect
wiring
Check all field wiring to the sensor and correct
any problems
Operation failed; Bead Fault.
TPPR cannot read
the bead current from
the connected mV
sensor
Check all field wiring to the sensor. It is
possible that the sensor has failed, Refer to the
manufacturer’s instructions