CONFIGURATION
Part. No. 2400M2501_6 Touchpoint Pro
74 Technical Handbook
9.2.22 Inhibit Signalling Settings
Access Level: Engineer
Parameter Name
Default
Setting
Value Range
Comment
Inhibit Signalling
Enable
Disabled
Enabled /
Disabled
If enabled, a specific signal level from the sensor will
activate an inhibit condition for the channel.
Inhibit Level Max
1.0 mA
1.0 to 3.9 mA
The recommended minimum difference between Inhibit
Level Max and Inhibit Level Min is 0.2 mA
Inhibit Level Min
2.0 mA
0.8 to 3.9 mA
9.2.23 Fault Signalling Settings 1
Access Level: Engineer
Parameter Name
Default
Setting
Value Range
Comment
Custom Event 1
Enable
Disabled
Enabled /
Disabled
If enabled, a specific signal level from the sensor will
activate a custom fault condition for the channel. An
example of a custom fault is the Beam Block condition
for an open path IR detector
Custom Event 2
Enable
Disabled
Enabled /
Disabled
Custom Event 3
Enable
Disabled
Enabled /
Disabled
9.2.24 Fault Signalling Settings 2
Access Level: Engineer
Parameter Name
Default Setting
Value Range
Comment
Custom Event 4 Enable
Disabled
Enabled /
Disabled
If enabled, a specific signal level from the sensor
will activate a custom fault condition for the
channel. An example of a custom fault is the
‘Beam Block’ condition for an open path IR
detector
Custom Event 5 Enable
Disabled
Enabled /
Disabled

Table of Contents

Other manuals for Honeywell touchpoint Pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell touchpoint Pro and is the answer not in the manual?

Honeywell touchpoint Pro Specifications

General IconGeneral
BrandHoneywell
Modeltouchpoint Pro
CategoryControl Systems
LanguageEnglish

Related product manuals