Function Parameter Index Reference
92 RS232 Communications Reference Manual 8/99
RESET2 32 REAL
integration time, 0 or 0.02 to 50 (minutes) or repeats per minute, 0
or 50 to 0.02 (repeats) [Tune Set 2]
use_propband 33 BOOL
Use Gain (0) or Proportional Band (1)
use_rpm 34 BOOL
Use minutes (0) or repeats per minute (1) for integral constant
sp_rate_dn 35 REAL
Set point low rate of change limit, 0 (off) to 99999 (eu/min)
sp_rate_up 36 REAL
Set point high rate of change limit, 0 (off) to 99999 (eu/min)
FF_GAIN 37 REAL
Feed forward gain, 0.0 to 10.0
RATIO 39 REAL
Gain value for Ratio PID (-20 to 20) (default 1) [ used when
RA_BIAS > 0]
LBIAS 40 REAL Bias value for Ratio PID when RA_BIAS = LOC_BIAS](-99999 to
99999) (0)
devbar_hi 41 REAL
High scale value for deviation bar graph (0 to 99999) (default 100)