Function Parameter Index Reference
78 RS232 Communications Reference Manual 8/99
5.36 MSF Function Block
Description
The MSF label stands for Mass Flow Calculation. This block is part of the Calculations category. It looks
like this graphically on the Control Builder.
Dynamic Parameters:
Table 5-44 MSF Dynamic Parameters
Parameter Index Type Use R/W Description
status 0 REAL C R block status (see section 5.2 for code list)
OUT 1 REAL O R output
X2REALIR
Y3REALIR
Z4REALIR
Static Configuration Parameters:
Table 5-45 MSF Static Configuration Parameters
Parameter Index Type Description
Kg 0 REAL Orifice Constant {-99999 to 999999}
Kx 1 REAL Delta Pressure Scaler {-99999 to 999999}
Ky 2 REAL Pressure Scaler {-99999 to 999999}
Kz 3 REAL Temperature Scaler {-99999 to 999999}
Bx 4 REAL Pressure Bias {-99999 to 999999}
By 5 REAL Delta Pressure Bias {-99999 to 999999}
Bz 6 REAL Temperature Bias {-99999 to 999999}
DROPOFF 7 REAL low dropoff value (EU) {0 to 99999} [default 0]